After an Aspen InfoPlus21 upgrade on a Subscriber system, Aspen Process Explorer Graphic fields are showing an old value
Download as pdf :
Products:
Aspen InfoPlus.21, Aspen Process Explorer
Last Updated:
05-Nov-2020
Last Updated:
05-Nov-2020
Versions:
Article ID:
000097792
Article ID:
000097792
Primary Subject:
Applicable Version(s):
All
Problem Statement:
After an Aspen InfoPlus21 upgrade on a Subscriber system the Aspen Process Explorer Graphic fields are showing an old value or ***. When the graphic is refreshed it will show the correct current value but will revert back to an old value or ****.
Solution:
If the Publisher system is replicating the IP_Value, IP_Value_Time, IP_Value_Quality fields then the *Map records on the Subscriber must be modified. The CurrentValue fields in AtMapDef records are typically set to the IP_Input fields that are not updating on the Subscriber. Therefore; the CurrentValue fields in the map records must be set to the IP_Value fields.
IP_AnalogMap example;
Map_CurrentValue IP_Value
Map_CurrentTimeStamp IP_Value_Time
Map_CurrentQuality IP_Value_Quality
KeyWords:
old
past