After an Aspen InfoPlus21 upgrade on a Subscriber system, Aspen Process Explorer Graphic fields are showing an old value

Download as pdf : 
Products: Aspen InfoPlus.21, Aspen Process Explorer 
Last Updated: 05-Nov-2020
Versions: 
Article ID: 000097792
Primary Subject: 
Applicable Version(s):
All 

Problem Statement:
After an Aspen InfoPlus21 upgrade on a Subscriber system the Aspen Process Explorer Graphic fields are showing an old value or ***.  When the graphic is refreshed it will show the correct current value but will revert back to an old value or ****.

Solution:
If the Publisher system is replicating the IP_Value, IP_Value_Time, IP_Value_Quality fields then the *Map records on the Subscriber must be modified.  The CurrentValue fields in AtMapDef records are typically set to the IP_Input fields that are not updating on the Subscriber.  Therefore; the CurrentValue fields in the map records must be set to the IP_Value fields.

IP_AnalogMap example;
Map_CurrentValue                     IP_Value

Map_CurrentTimeStamp            IP_Value_Time
Map_CurrentQuality                   IP_Value_Quality

KeyWords:
old
past